One area of confusion in production safety testing is the dielectric strength test, sometimes known the as dielectric withstand test or “hipot” test.
This test is usually applied between the secondary output and chassis ground and then between the AC connection (primary) and ground / secondary. This test can identify any assembly errors such as a pinched wire.
It is important to ensure to short the line and neutral together during the test, and when making the primary to secondary test, connect the secondary side to chassis. Short the output terminals together if testing a standalone power supply. Failure to do this can result in damage to the power supply.
A routine question is “should the test voltage be AC or DC?” The majority of power supply manufacturers use a DC voltage because the leakage current through the “Y” capacitors can mask another fault.
The “Y” capacitors are identified in a very simplified diagram below are used to reduce EMI and electrical noise.
As can be seen, applying an AC input to chassis hipot test would result in mill-Amps of current flowing through the capacitors
The majority of safety standards allow DC hipot voltages. Instead of applying 1500VAC, one would use the peak voltage of the AC, √2 x 1500 = 2121VDC. Add 10% to reduce the test time from 1 minute to 1 – 2 seconds.
Apply the DC voltage slowly to allow the capacitors to charge up without tripping the current limit of the test equipment. Remember to discharge the capacitors after the test.
Wednesday, March 3, 2010
Subscribe to:
Posts (Atom)
Popular Posts
-
There are three common methods of charging a battery; constant voltage, constant current and a combination of constant voltage/constant cu...
-
There are two frequently used terms for types of DC-DC converters; non-isolated and isolated. This “isolation” refers to the existence of a...
-
Switchmode power supplies without Power Factor Correction (PFC) tend to draw the AC input current in short bursts or spikes relative to the ...
-
A power converter’s efficiency (AC-DC or DC-DC) is determined by comparing its input power to its output power. More precisely, the efficien...
-
Many rack-mounted power systems are specified as being 1U, 2U, 3U, etc. What does this mean? For electronic equipment racks (e.g., 19 or 23 ...
-
One question I am frequently asked is: “The customer is looking for a Class two power supply; what can you offer him?” My response is alwa...
-
Conventional AC-DC power supplies and DC-DC converters provide an output that is regulated to provide a “constant-voltage.” However, LED...
-
Most AC-DC power supplies and DC-DC converters have internal current-limiting circuits to protect the power device, and to some degree its l...
-
Most medium to high power AC-DC power supplies and some DC-DC converters include "Remote Sense" connection points (+ and - Sense) ...
-
The Power Guy blog focuses on modern switch-mode power supplies and converters. However, to provide the newbie (newcomer) with some backgro...