SELV stands for Safety Extra Low Voltage. Some AC-DC power supply installation manuals contain warnings concerning SELV. For example, there may be a warning about connecting two outputs in series because the resulting higher voltage may exceed the defined SELV safe level, which is less than or equal to 60VDC. In addition, there may be warnings about protecting the output terminals and other accessible conductors in the power supply with covers to prevent them from being touched by operating personnel or accidently shorted by a dropped tool, etc.
UL 60950-1 states that a SELV circuit is a “secondary circuit which is so designed and protected that under normal and single fault conditions, its voltages do not exceed a safe value.” A “secondary circuit” has no direct connection to the primary power (AC mains) and derives its power via a transformer, converter or equivalent isolation device.
Most switchmode low voltage AC-DC power supplies with outputs up to 48VDC meet the SELV requirements. With a 48V output the OVP setting can be up to 120% of nominal, which would allow the output to reach 57.6V before the power supply shuts down; this would still conform to the maximum 60VDC for SELV power.
In addition, an SELV output is achieved through electrical isolation with double or reinforced insulation between the primary and secondary side of the transformers. Moreover, to meet SELV specifications, the voltage between any two accessible parts/conductors or between a single accessible part/conductor and earth must not exceed a safe value, which is defined as 42.4 VAC peak or 60VDC for no longer than 200 ms during normal operation. Under a single fault condition, these limits are allowed to go higher to 71VAC peak or 120VDC for no longer than 20 ms.
Don’t be surprised if you find other electrical specs that define SELV differently. The above definitions/descriptions refer to SELV as defined by UL 60950-1 and other associated specs regarding low voltage power supplies.
Tuesday, March 5, 2013
Subscribe to:
Post Comments (Atom)
Popular Posts
-
There are three common methods of charging a battery; constant voltage, constant current and a combination of constant voltage/constant cu...
-
There are two frequently used terms for types of DC-DC converters; non-isolated and isolated. This “isolation” refers to the existence of a...
-
Switchmode power supplies without Power Factor Correction (PFC) tend to draw the AC input current in short bursts or spikes relative to the ...
-
A power converter’s efficiency (AC-DC or DC-DC) is determined by comparing its input power to its output power. More precisely, the efficien...
-
Many rack-mounted power systems are specified as being 1U, 2U, 3U, etc. What does this mean? For electronic equipment racks (e.g., 19 or 23 ...
-
One question I am frequently asked is: “The customer is looking for a Class two power supply; what can you offer him?” My response is alwa...
-
Conventional AC-DC power supplies and DC-DC converters provide an output that is regulated to provide a “constant-voltage.” However, LED...
-
Most AC-DC power supplies and DC-DC converters have internal current-limiting circuits to protect the power device, and to some degree its l...
-
Most medium to high power AC-DC power supplies and some DC-DC converters include "Remote Sense" connection points (+ and - Sense) ...
-
The Power Guy blog focuses on modern switch-mode power supplies and converters. However, to provide the newbie (newcomer) with some backgro...
No comments:
Post a Comment